Video: How is an ATV212 or ATV21 reset to factory defaults?

Article available in these languages: Fins

Issue:
ATV212 or ATV21 reset factory defaults.

Product Line:
ATV212, ATV21, S-Flex

Environment:
All part numbers

Cause:
Change in programming or application that requires the drive to be reset to factory default settings.

Resolution:
Set tYP = 3 to return to factory settings (remember to press and hold enter for 2 seconds).
Then set  tYP = 2 to configure for 60Hz.
Proceed with any further programming from here.

ATV212 Typ parameter

Consult the ATV212 Programming Manual or ATV21 Programming Manual for additional details:


Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

  • Selecteer zelf het juiste product

    Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

  • Offerte aanvragen

    Dien uw aanvraag online in en een expert zal contact met u opnemen.

  • Verkooppunten

    Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

  • Help Center

    Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings