Video: How do I change from ramp stop to freewheel stop on the ATV61 and ATV71 drives?
Issue:
Programming Freewheel Stop on Altivar 61 & 71 Drives

Product line:
ATV61, ATV71

Environment:
All models, all serial numbers

Cause:
Need to change the stop type to support application.

Resolution:
  • Go into the Application menu 1.7
  • Enter Stop configuration
  • Enter " type of stop"
  • Change SST (type of stop) value to NST and enter.
Additional  resources (attached):  ATV71 programming manual  and ATV61 programming manual.

type of stop

Schneider Electric Belgium

bijlage(n)
ATV61_Programming_manual_EN_1760649_09.pdf [2.37 MB]
ATV71_Programming_manual_EN_1755855_10.pdf [5.94 MB]
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

  • Selecteer zelf het juiste product

    Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

  • Offerte aanvragen

    Dien uw aanvraag online in en een expert zal contact met u opnemen.

  • Verkooppunten

    Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

  • Help Center

    Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings