Issue:
E-Flex drive is tripping on OHF
Product line:
Altivar ATV61 E-Flex enclosed drives
Environment:
All models, all serial numbers
Cause:
Cooling fans are not running or the thermal sensor may be bad
Resolution:
Check the heat sink cooling fans to see if they are running. If they are not running remove the fan connector and check to see if you have voltage on the terminals. If you have good voltage then the heat sink cooling fans are bad. If you don't have voltage on the terminals you may have a bad power board and or drive. To check the thermal sensor you can monitor the drives thermal temp % in Menu 1.2 monitoring. If the thermal % is jumping around erratic you may have a bad thermal sensor.
E-Flex drive is tripping on OHF
Product line:
Altivar ATV61 E-Flex enclosed drives
Environment:
All models, all serial numbers
Cause:
Cooling fans are not running or the thermal sensor may be bad
Resolution:
Check the heat sink cooling fans to see if they are running. If they are not running remove the fan connector and check to see if you have voltage on the terminals. If you have good voltage then the heat sink cooling fans are bad. If you don't have voltage on the terminals you may have a bad power board and or drive. To check the thermal sensor you can monitor the drives thermal temp % in Menu 1.2 monitoring. If the thermal % is jumping around erratic you may have a bad thermal sensor.
Gepubliceerd voor: Schneider Electric Belgium
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.