{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

Why is the CB status of Sepam Series 40 displayed with ‘?’ mark in PowerLogic SCADA?

If you have a problem as per below, you need to check 2 things.

a. The hard-wired signals from the CB which are for CB On/Off status must be connected to Sepam 40 following the default IO setting. (Please take a Sepam 40 manual for more details.)

b. Device closed tag must be added into your project.

You can find this tag under Sepam Series 40 with default IO device type -> Miscellaneous -> Real Time Tags in PowerLogic SCADA Profile Editor.

Check also last Updated information from our PowerLogic L3 Team

Key words and phrases:

question mark, meaning, signification, signify, mean, what

AEBL3

Original Author: YJ

Public

All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL200477 V2.0, Originally authored by KBAdPM on 11/11/2009, Last Edited by DaMi on 01/22/2010
Related ranges: Sepam series 40, PowerLogic SCADA 7.1

Schneider Electric Belgium

Ontdek meer
Productfamilie
AVEVA™ Plant SCADASepam series 40
Ontdek meer
Productfamilie
AVEVA™ Plant SCADASepam series 40