Altivar 71 v2.5 behavior with CANopen.

Goals and Symptoms

Motion Control / Altivar 71 - Altivar 71 v2.5 behavior with CANopen.
It n' is not possible to connect an Altivar 71 version 2.5 on a system Unity Pro v3.X with M340 as well as on Advantys and STB.

Causes and Fixes

Causes:
It is after an evolution of major index of the object " 1018sub3" of the drive.

It is thus not possible to replace an ATV71 v1.x by an ATV71 v2.5 on an existing installation or to create a new application with this version of drive.


Solution

The solution consists in upgrading Altivar 71 with a minimal version v2.5 (IE37), for that, contact your respective Schneider Engineering service, this operation takes less than 20 mn.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings