Issue
How to find and use the PDO reference for an 'Advantys' IO module in a 'Unity' application..
Product Line
Advantys Configuartion Software
Environment
Windows 7
Resolution
Find the 'PDO' references for the 'Advantys' IO modules using the following steps:
- Click on the island I/O module in the 'Advantys Configuration Software'.
- Click on 'Island\ IO Image Overview'.
- Clcik on the tab lableled 'Fieldbus Image' in the 'IO Image Overview' window.
- Place the cursor on one of the 'Input Data' in the table and a message will appear to describe
6000 with a subindex.)
Export the 'Advantys' configuration into a '.dcf' file using the following steps:
- Click on 'File\Export' in the 'Advantys' software window.
- Select 'DCF' for the 'Export Format'.
- Enter the pathname for the 'Directory' and 'Filename'.
- Click on 'OK' to create the file.
Import the '.dcf' file into the 'M340' configuration using the following steps:
- Start Unity and open the M340 application.
- Expand the 'CANopen' network in Unity.
- Double click on the CANopen drop to open the window.
- Double click on the 'Advantys STB island' image in the CANopen network configuration window.
- Click on 'Channel 0' in the CANopen Network Interface Module' window.
- Click on the 'PDO' tab to open it.
- Right click on the 'PDO' window and select 'Import DCF' to import the dcf file.
also be shown mapped to a '%IW' word that is shown in the 'Topo Adr' column.
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.