“Use GPS Quality Flag,” has been introduced in the Setup Register for ION8600 version 332 ( v332).
Issue
For some reason, unexpectedly the meter (ION8600) stops communicating.
Product Line
ION8600
ION Setup
Environment
Configuration
Cause
The clock source couldn’t sync.
Resolution
A new setup register has been added to the clock module on the ION8600 v332. This register is called Use GPS Quality Flag and provides two configuration options: Use Flag and Ignore Flag.
In previous firmware versions, meters configured to synchronize with a GPS time source would only accept time synchronization when the GPS was locked to a satellite. If the GPS source became unlocked, the meter would stop accepting time sync signals until the lock was restored.
Go to ION Setup Advanced configuration > Clock Modules > Setup register. See highlighted on figure 1 below.
Fig. 1
To select one of the behaviors: Highlight CL1 Use GPS Quality Flag > Edit > Then select either one. See figure 2 below:
This new feature allows users to choose between two behaviors:
Use Flag: The meter will only accept time synchronization if the GPS source quality flag indicates a locked state.
Ignore Flag: The meter will accept time synchronization regardless of the GPS source quality flag state.
Fig. 2
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.