Issue:
Needs a jog input for the Altivar 12 drive.
Product Line:
ATV12, Altivar 12
Environment:
All models
Cause:
Using a logic input to Jog the motor.
Resolution:
Assign a Logic input under the Jog function (COnF > FULL > FUn > JOG). Jog can be assigned to L1h, L2h, L3h or L4h. The Jog function is a speed reference of 5Hz with 0.1s ACC and DEC. This value cannot be adjusted. If you need a jog faster than 5Hz, use a Preset Speed.
In order to Jog, the drive needs to have a direction command (Run Forward or Run Reverse input closed).
The Jog function is not compatible with PI Regulator.