Issue:
Torque control not working
Product Line:
ATV71
Environment:
All models and serial numbers
Cause:
Motor control type not set to SVCI
torque/speed not enabled [Trq/spd switching]
Torque reference channel not assigned [Torque ref. channel]
Speed reference not assigned
Resolution:
Set motor control type t SVCI
Enable torque speed switching. Set to "Yes" for permanent torque control or assign a logic input.
Assign a torque reference channel. This can be set as the low speed, preset speed, analog input, serial comm or encoder feedback.
Assign a speed reference (do not assign it to the same as torque reference channel)
Torque control not working
Product Line:
ATV71
Environment:
All models and serial numbers
Cause:
Motor control type not set to SVCI
torque/speed not enabled [Trq/spd switching]
Torque reference channel not assigned [Torque ref. channel]
Speed reference not assigned
Resolution:
Set motor control type t SVCI
Enable torque speed switching. Set to "Yes" for permanent torque control or assign a logic input.
Assign a torque reference channel. This can be set as the low speed, preset speed, analog input, serial comm or encoder feedback.
Assign a speed reference (do not assign it to the same as torque reference channel)
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.