Issue:
ATV61 and ATV71 drives controlled in a NET command control mode.
Product Line:
Altivar ATV61 and ATV71 with an Serial communications option card.
Environment:
All
Cause:
The drive is showing Terminal control mode they need to set it up for NET control.
Resolution:
Basic Programming settings will be
Set up your communications card in menu 1.9
In Menu 1.6:
-Set your Ref 1 1 channel to com card
-Set your Profile to be not separate
or
Set your Profile to be Separate then CMD switching to a logic input or choose channel reference as com card.
Attached is the ATV61 Programming Manual to assist if needed.
ATV61 and ATV71 drives controlled in a NET command control mode.
Product Line:
Altivar ATV61 and ATV71 with an Serial communications option card.
Environment:
All
Cause:
The drive is showing Terminal control mode they need to set it up for NET control.
Resolution:
Basic Programming settings will be
Set up your communications card in menu 1.9
In Menu 1.6:
-Set your Ref 1 1 channel to com card
-Set your Profile to be not separate
or
Set your Profile to be Separate then CMD switching to a logic input or choose channel reference as com card.
Attached is the ATV61 Programming Manual to assist if needed.
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.