Issue:
Getting an SCF (Short Circuit Fault) on an ATS22.
Product Line:
ATS22 Soft Start
Environment:
All models and serial numbers.
Cause:
NA
Resolution:
There are a number of reasons for a short circuit fault detected on an ATS22 Soft Start:
1. Megger the motor and motor cables. The motor may have a short circuit in any or all windings phase to phase or phase to ground. The motor wires could be shorted to ground.
2. SCR's may be shorted, or the internal shorting contactor may be stuck closed. Measure resistance across each phase of the Softstart (L1 to T1, L2 to T2, L3 to T3). Check for, at minimum, 50K Ohms resistance on each phase.
Getting an SCF (Short Circuit Fault) on an ATS22.
Product Line:
ATS22 Soft Start
Environment:
All models and serial numbers.
Cause:
NA
Resolution:
There are a number of reasons for a short circuit fault detected on an ATS22 Soft Start:
1. Megger the motor and motor cables. The motor may have a short circuit in any or all windings phase to phase or phase to ground. The motor wires could be shorted to ground.
2. SCR's may be shorted, or the internal shorting contactor may be stuck closed. Measure resistance across each phase of the Softstart (L1 to T1, L2 to T2, L3 to T3). Check for, at minimum, 50K Ohms resistance on each phase.
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.