Video: How do you set up the ATV61/71 drive so that the set point for PID can be adjusted using the keypad?
Issue:
Trying to set up the ATV61/71 drive so that the set point for PID can be adjusted using the keypad.
Product Line:
ALTIVAR 61, ALTIVAR 71
Environment:
All serial numbers
Resolution:
In the PID Regulator function, set parameter "Act. Internal PID ref" to NO. Use "Ref 1 channel" set to HMI.
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)“
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.