How can we have diagnostic information for TMC2xxx additional cartridge analog I/O module within a TM221Cxxx PLC SoMachine/Machine Expert - Basic application program ?
For each channel, it exists a dedicated system word object available for diagnostic .
It’s %IWS.0.i for an analog input channel
It’s %QWS.0.i for an analog output channel
With i defined by this way:
i=100 for the 1st channel of the cartridge located 1st slot
i=101 for the 2nd channel of the cartridge located 1st slot
i=200 for the 1st channel of the cartridge located 2nd slot
i=201 for the 2nd channel of the cartridge located 2nd slot
The definition of the code status/diagnostic value is as below:
For %IWS word content definition
| 0 | Normal |
| 1 | Data conversion in progress |
| 2 | Initialization in progress |
| 3 | Input operation setting error or module without input |
| 4 | not used |
| 5 | High limit reached |
| 6 | Low limit reached |
| 7 | Non-volatile memory error |
For %QWS word content definition
| 0 | Normal state |
| 1 | not used |
| 2 | Initialization in progress( after power on) |
| 3 | Output operation setting error or module without output |
| 4 | not used |
| 5 | not used |
| 6 | not used |
| 7 | Non-volatile memory error |
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.