Thermocouple category definition
It exists two main categories of thermocouple sensors
1) “Isolated “ or “ungrounded” thermocouple : the 2 wires junction is insulated from the Metalic part of the sensor and so from the shield (present all around and along the sensor’s cable )
2) “grounded” or “non isolated” thermocouple : the 2 wires junction is connected to the metallic part , and so indirectly connected to the shield all around and along the thermocouple cable
Within the TMC2TI2 cartridge and TM3TI4x, TM3TI8Tx, TM3TM3x modules it’s advised to use exclusively “isolated” thermocouples ( and not a “grounded thermocouple)
else when more than one sensor is connected onto different channel of one such module, the result is wrong temperature measurements for all the channels
Deeper explanation :inside the TMC2TI2/TM3xx all their channel inputs pins named Ix- (with x =0,1,2,3,4 to n, n number of analog channel supported by the module) are all internally connected together , as soon as 2 “grounded” thermocouple sensors are connected to the same module/cartridge, (same way all sensors would have been mounted in parallel onto the same channel input) , this would provide wrong temperature measurements, by giving nearly same temperature measurements values for all the sensors inputs what ever real temperature on each sensor !
Only with TMC4TI2 cartridge , it’s possible to used both “isolated” or “grounded” kind of thermocouple sensors .
There is no restriction because TMC4TI2 channel inputs pins I0- and I1- are non connected internally, they are isolated .
It exists two main categories of thermocouple sensors
1) “Isolated “ or “ungrounded” thermocouple : the 2 wires junction is insulated from the Metalic part of the sensor and so from the shield (present all around and along the sensor’s cable )
2) “grounded” or “non isolated” thermocouple : the 2 wires junction is connected to the metallic part , and so indirectly connected to the shield all around and along the thermocouple cable
Within the TMC2TI2 cartridge and TM3TI4x, TM3TI8Tx, TM3TM3x modules it’s advised to use exclusively “isolated” thermocouples ( and not a “grounded thermocouple)
else when more than one sensor is connected onto different channel of one such module, the result is wrong temperature measurements for all the channels
Deeper explanation :inside the TMC2TI2/TM3xx all their channel inputs pins named Ix- (with x =0,1,2,3,4 to n, n number of analog channel supported by the module) are all internally connected together , as soon as 2 “grounded” thermocouple sensors are connected to the same module/cartridge, (same way all sensors would have been mounted in parallel onto the same channel input) , this would provide wrong temperature measurements, by giving nearly same temperature measurements values for all the sensors inputs what ever real temperature on each sensor !
Only with TMC4TI2 cartridge , it’s possible to used both “isolated” or “grounded” kind of thermocouple sensors .
There is no restriction because TMC4TI2 channel inputs pins I0- and I1- are non connected internally, they are isolated .
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.