What are the limitations of ISAGRAF ?
For a project
| - |
| Programs |
| 255 |
| grouping_main,_sub_and_child_programs |
| - |
| Levels_in_the_hierarchy |
| 20 |
For names
| - |
| Project |
| 8 char |
| - |
| Program |
| 8 char |
| - |
| Variable |
| 32 char |
| 60 characters for comment |
| - |
| Defined word label |
| 16 char |
| - |
| Defined equivalence |
| 255 char |
| 60 characters for comment |
| - |
| Conversion table |
| 16 char |
| - |
| List of variables |
| 16 char |
| - |
| function / f.block (lib) |
| 8 char |
| this applies to C functions, C function blocks or functions written in IEC languages |
| - |
| function parameter (lib) |
| 16 char |
| this applies to C functions, C function blocks or functions written in IEC languages |
| - |
| IO board |
| 8 char |
| - |
| IO configuration |
| 8 char |
| - |
| Board oem parameter |
| 16 char |
| - |
| Conversion function |
| 8 char |
| - |
| - |
| SFC_rows |
| 600 |
| - |
| SFC_columns |
| 20 |
| - |
| SFC_steps |
| 4095 |
| for_the_whole_project,_grouping_steps,_initial_steps,beginning_and_ending_steps |
| - |
| SFC_transitions |
| 4095 |
| for_the_whole_application |
| - |
| LD/FBD_editing |
| 200_cols |
| - |
| 2000_rows |
| this_is_the_size_of_the_editing_area_in_cell_units. |
| - |
| Quick_LD_editing |
| no_limit |
| limits_are_imposed_by_the_PC_capacity |
| - |
| IL_labels |
| 251 |
| in_the_same_IL_program |
| - |
| Text_editing |
| 40KBytes |
| or_less_according_to_the_system_configuration |
| - |
| - |
| Boolean variables |
| 65535 |
| - |
| Analog variables |
| 65535 |
| grouping integer and real variables |
| - |
| Timers |
| 65535 |
| - |
| Message variables |
| 65535 |
| - |
| Defined words |
| 4095 |
| in the same list (same range) |
| - |
| Defined words |
| 255 |
| used in the same program |
| - |
| Conversion tables |
| 127 |
| used in the application |
| - |
| Points in one table |
| 32 |
| defined in the same conversion table |
| - |
Number of I/O boards including single boards and items of complex equipments cannot exceed 256.
| - |
| IO_Boards |
| 256 |
| defined_for_the_same_application_(boards_or_complex_equipment) |
| - |
| IO_channels |
| 128 |
| on_the_same_board |
| - |
| Functions (IEC lang.) |
| 255 |
| installed together in the library |
| - |
| Function blocks |
| - |
| (IEC lang.) |
| 255 |
| installed together in the library |
| - |
| C functions |
| 255 |
| installed together in the library |
| - |
| C function blocks |
| 255 |
| installed together in the library |
| - |
| function blocks |
| - |
| instances |
| 4095 |
| for the same type of function block in the same application |
| - |
| Function input parameters |
| 31 |
| this applies to C functions and functions written in IEC languages |
| - |
| Function block parameters |
| 32 |
| freely distributed between input and output parameters. At least 1 output parameter is required. |
| - |
| Conversion function |
| 128 |
| installed together in the library |
| - |
| IO configurations |
| 255 |
| installed together in the library |
| - |
| IO boards |
| 255 |
| installed together in the library |
| - |
| Complex IO equipt. |
| 255 |
| installed together in the library |
| - |
| Board oem parameters |
| 16 |
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.