How to Write a number to 3nnnn register in SCADAPack with TelePACE firmware?

The 30000-class register table is for Input Registers and is read-only to external Modbus masters. If you need a writable target over Modbus, use 40000-class table for Holding Registers.

That being said, you can have TelePACE ladder logic push data into a 3nnnn register if required. Using the OVER function block in TelePACE Studio, a register value can be written into a 3nnnn register . The source register can be any valid 0nnnn (coil register), 1nnnn (status register), 3nnnn (input register) or 4nnnn (holding register)

Please note: Using the OVER block will override the value in the destination input register. This is considered a force in the controller and will turn on the SCADAPack's FORCE LED .

Schneider Electric Belgium

Ontdek meer
Product:
Ontdek meer
Product:

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings