PME as an EWS server connected with SoapUI as an client got Error message 401.2

Issue:
When using PME as EWS server and SoapUI as an EWS client,SoapUI got the following error message:

<b> Error message 401.2 .: </b>Unauthorized: Logon failed due to server configuration. &nbsp;Verify that you have permission to view this directory or page based on the credentials you supplied and the authentication methods enabled on the Web server. &nbsp;Contact the Web server's administrator for additional assistance.<br><br>

Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0

Cause:
This behavior is caused by Unauthorized, you have to put in the user name and password which has been authorized.

Resolution:
In SoapUI client, put in the username and password (e.g. username = supervisor; pw = 0​), every time before you use any Method or brose the items: