What can prevent the drive tripping on input phase fault?

Issue:
The drive does not trip when an input phase is removed.

Product Line:
Altivar Drives

Environment:
All models and serial numbers

Cause:
1.  Parameter IPL is set to no
Depending on the device type:
1)  Input phase loss works by detecting the ripple in the DC Bus. If the load is not high enough, it can't detect an input phase fault.
2)  Input phase loss works with the input phase detection on the rectifier circuit (ATV61/71/600/900/MX eco/MX pro) if the rectifier is thyristor controlled (power approximately >22kW).

Resolution:
1. Set Parameter IPL to yes
2. Provide additional motor load.


Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings