Issue:
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.
Resolution:
The warning LED is triggered when a Warning Group item is activated. The factory default has many items selected for monitoring under Warning Group 1. A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.
From the Main menu:
See attachment
Now the red flashing warning light will turn off.
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.
Resolution:
The warning LED is triggered when a Warning Group item is activated. The factory default has many items selected for monitoring under Warning Group 1. A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.
From the Main menu:
- Scroll to Complete Settings and press OK
- Select Error Warning Handling and press OK
- Select Warnings Group Configuration and press OK
- Select Warn group 1 definition and press OK
- Now (almost halfway down the list) uncheck "AI1 4-20 Warning", "AI2 4-20 Warning", and "AI3 4- 20 Warning" boxes.
See attachment
Now the red flashing warning light will turn off.
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.