Issue:
Setting up AQ1, AQ2, and AQ3 on the Altivar Process Drive.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
Altivar Process Drive
Cause:
N/A
Resolution:
To access analog output configurations,
[Complete settings] [Input/Output] [AI/AQ] [AQ1 configuration]
[AQ1 Assignment] AO1 - Analog Assignment - Adjust the analog output assignment (Can be set to motor current, freq, torque etc...)
[AQ1 Type] AO1t - Analog Output 1 Type - Adjust the analog output type between current and voltage
[Scaling AQ1 min] ASL1 - Scaling of the lower limit of the assigned parameter, as a % of the maximum possible variation.
[Scaling AQ1 max] ASH1 - Scaling of the upper limit of the assigned parameter, as a % of the maximum possible variation.
[AQ1 Filter] AO1F - AQ1 cutoff time of the low-filter.
Notes:
Works the same with AQ2 and AQ3

Setting up AQ1, AQ2, and AQ3 on the Altivar Process Drive.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
Altivar Process Drive
Cause:
N/A
Resolution:
To access analog output configurations,
[Complete settings] [Input/Output] [AI/AQ] [AQ1 configuration]
[AQ1 Assignment] AO1 - Analog Assignment - Adjust the analog output assignment (Can be set to motor current, freq, torque etc...)
[AQ1 Type] AO1t - Analog Output 1 Type - Adjust the analog output type between current and voltage
- Current
- [AQ1 min output] AOL1 - Analog Minimum Output - Minimum Current Scaling at 0%
- [AQ1 max output] AOH1 - Analog Maximum Output - Maximum Current Scaling at 100%
- For example If using 4-20ma out to follow speed reference set the following:
- AO1 - Motor Frequency [OFr]
- AO1t - Current [0A]
- AOL1 - 4
- AOH1 - 20
- Voltage
- [AQ1 min output] UOL1- Analog Minimum Output - Minimum Current Scaling at 0%
- [AQ1 max output] UOH1- Analog Maximum Output - Maximum Current Scaling at 100%
- For example If using 0-10v out to follow motor current set the following:
- AO1 - Motor Current [OCr]
- AO1t - Voltage [10U]
- UOL1 - 0
- UOH1 - 10
[Scaling AQ1 min] ASL1 - Scaling of the lower limit of the assigned parameter, as a % of the maximum possible variation.
[Scaling AQ1 max] ASH1 - Scaling of the upper limit of the assigned parameter, as a % of the maximum possible variation.
[AQ1 Filter] AO1F - AQ1 cutoff time of the low-filter.
Notes:
Works the same with AQ2 and AQ3
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.