Why does the output of my Unity Elementary Function (EF) continue to show power flow when EN is disabled?
Notice that the output of the EF is showing an active state even though the EN pin is disabled. Selecting this option in your Project settings will correct condition.
Tools\Project Settings\Program\Languages\Common

The attached PDF will show the effect of not selecting the Project Setting "Maintain Output Links on Disabled EF"

Schneider Electric Belgium

bijlage(n)
Maintain_Output_Links on_Disabled_EF_is _off .pdf [42.75 KB]