Video: How to use the DATA_EXCH function block on the M580 via the NOC module to read data from a another Ethernet IP device
Is there a working example of the DATA_EXCH function block on the M580 using CIP explicit messaging?
Product Line:
Ethernet IP NOC module, M580
Environment:
Unity Pro software
Resolution:
Follow steps below:
- Create a M580 project and add a NOC module
- Add an IP address to the NOC module and disable security in the DTM browser
- Create a section, in this example, ST was used.
- Add the DATA_EXCH function block and configured it as shown below
send_buffer[0] := 16#024E; (*High Byte - Path Size, Low Byte - Service Code: Read Holding Registers *)
send_buffer[1] := 16#4420; (*High Byte - Class, Low Byte - Class Segment *)
send_buffer[2] := 16#0124; (*High Byte - Instance, Low Byte - Instance Segment *)
send_buffer[3] := 16#0032; (*Location of the first word to read, in this case 50 *)
send_buffer[4] := 16#0001; (*Number to read, in this case 1 *)
management_parameters[2] := 10; (* timeout - 1 second 100 x 10 *)
management_parameters[3] := 10; (* length of
senbd buffer in bytes *)DATA_EXCH (EN := enable,
ADR := converted_address, (* result of ADDM function in "init" section *)
TYP := ActionType, (* Value of 1 - transmission followed by await reception *)
EMIS := send_buffer, (*message to send *)
GEST := management_parameters, (* control block *)
RECP => receive_buffer); (* buffer for returned message *)
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.