Issue
PME is configured to use SSL and the HTTP binding is removed from IIS, the links from the Management Console to the web applications will no longer work.
Product Line
Power monitoring Expert 8.x
Environment
Management Console
Internet Explorer
Cause
Links in Management Console point to a HTTP location, which was deactivated, and cannot be changed.
The affected web applications are:
* Rate Editor
* Hierarchy Manager
* Alarm Configuration
Resolution
All of these web applications can be accessed from the Settings area of Web Applications in PME 8.2. Note that it is generally bad practice to access web applications directly from the server, and the links in the Management Console will be removed in a future PME release.
PME is configured to use SSL and the HTTP binding is removed from IIS, the links from the Management Console to the web applications will no longer work.
Product Line
Power monitoring Expert 8.x
Environment
Management Console
Internet Explorer
Cause
Links in Management Console point to a HTTP location, which was deactivated, and cannot be changed.
The affected web applications are:
* Rate Editor
* Hierarchy Manager
* Alarm Configuration
Resolution
All of these web applications can be accessed from the Settings area of Web Applications in PME 8.2. Note that it is generally bad practice to access web applications directly from the server, and the links in the Management Console will be removed in a future PME release.
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.