After conversion of a SoMachine V3.1 project including an M258 to SoMachine V4.2, TM5 modules configuration tabs are wrong.
For example with DI12DE :
Normally it should be like this :
But this is what conversion gives:
Wrong "Outputs" folder is there.
Furthermore integrated TM5 modules data is not exchanged when converted project is downloaded to a controller.
It happens when conversion from V3.1 to V4.2 is not executed “directly” :
When V3.1 project is opened in SoMachine v4.2, a pop-up asks for project conversion. “Yes” should be answered right now.
If conversion is done later using “right click -> update device” then trouble with TM5 modules happen.
This will be corrected in SoMachine V5.
For example with DI12DE :
Normally it should be like this :
But this is what conversion gives:
Wrong "Outputs" folder is there.
Furthermore integrated TM5 modules data is not exchanged when converted project is downloaded to a controller.
It happens when conversion from V3.1 to V4.2 is not executed “directly” :
When V3.1 project is opened in SoMachine v4.2, a pop-up asks for project conversion. “Yes” should be answered right now.
If conversion is done later using “right click -> update device” then trouble with TM5 modules happen.
This will be corrected in SoMachine V5.
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.