Cannot see load values in Connexium Network Manager
Cannot see load values in Connexium Network Manager 'Load' window.
Product:
Connexium Network Manager 2.0
Environment:
Windows 10
Resolution:
The Connexium Network Manager 'Load' window does not show any traffic load between the ports of two Ethernet devices.
The reasons for not being able to see a load value between the Ethernet ports of two different devices (i.e., Connexium TCSESM switch and NOE77101) could be either:
- Improper configuration.
- Incorrect VLAN has been selected.
- No traffic load on the network segment between the ports
- Check the load values of the connection between the server and the Connexium TCESEM switch port by opening the web interface.
- Right click on the switch icon and selecting 'Web Interface'
- Navigate to "Diagnostics --> Ports --> Utilization" and see whether there is load on the port.
- Go back to the Connexium Network Manager 'Map' window.
- Double click on the link between the two Ethernet ports to see what amount of traffic is display. (Note: The traffic is normally split between incoming and outgoing load.) to open the load window.
- Compare the displayed values with the values in Connexium Network Manager 'Load' window with the values found in the Connexium TCSESM Web Server 'Utilization' window.
- Determine if the values are matched between the two windows.
- If the values are lower than expected, then there is a probability that there is no traffic being transmitted between the ports.
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.