Conformance Classes
The following Modbus conformance classes (and function codes) are supported by the Modbus/TCP Server and the native Modbus Slave.
路Class 0 (function codes 3 and 16)
路Class 1 (function codes 1, 2, 4, 5, 6, and 7)
路Class 2 (function code 15 only).
Function Code 7
This function code allows a client to request the SCADAPack E Modbus server/slave to return an exception status that is stored in a pre-determined range of 8 coils. RTU binary system (scratchpad) points 50000 to 50007 are allocated for this purpose.
路RTU binary point 50000 will map to the least significant bit of the response byte.
路RTU binary point 50007 will map to the most significant bit of the response byte.
Function Code 8
This function code allows a client to request the SCADAPack E Modbus slave to return a response to a "Return Query Data" request. The following functionality is provided:
路Function Code 8 is supported on Modbus Slave serial connections only
路A Function Code 8 request on a Modbus/TCP connection returns Exception response with error code 1 (Illegal function)
路Sub function 00 00 is the only sub function supported for a Modbus function code 8 request
路A response will only be generated to a FC8 Sub-function 00 00 request when the data field size is 2
路The Response to a FC8 Sub-function 00 00 (data field size 2) request is an echo of the request
路A request for Sub functions other than 00 00 returns an Exception response with error code 3 (Illegal Data Value)
路There will be no response to a FC8 Sub-function 00 00 request if the data field size is not 2