Issue
Some sites and or devices cannot connect in PME. The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.
Product Line
PME7.x
PME8.x
PME 9.0, PME2020, PME2021, PME2022, PME2023
Environment
Device / site communications
Cause
Customers may block the Ping command through the network for security reasons. If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.
Resolution
Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.
Some sites and or devices cannot connect in PME. The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.
Product Line
PME7.x
PME8.x
PME 9.0, PME2020, PME2021, PME2022, PME2023
Environment
Device / site communications
Cause
Customers may block the Ping command through the network for security reasons. If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.
Resolution
Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.