Issues:
When configuring an ATV32 or ATV320: How do you set the drive to always stop by Freewheel and assign a Run Permissive?
Product Line:
ATV32 ATV320
Environment:
ALL
Cause:
Input to Stop
Resolution:
On the keypad of the drive, you will press the dial and go to the following:
Freewheel Stop Always: ConF > FULL > FUn- > Stt > Stt and set to nSt
Run permissive input: ConF > FULL > FUn- > Stt > nSt and assign that to a Logic/Digital Input.
**Keep in mind that Freewheel Stop [nSt] is an active Low input, so if you do not have the wiring in place, the drive will be locked in nSt state. Add a jumper from 24v to DIx/LIx assigned input until you have the actual contact installed.
When configuring an ATV32 or ATV320: How do you set the drive to always stop by Freewheel and assign a Run Permissive?
Product Line:
ATV32 ATV320
Environment:
ALL
Cause:
Input to Stop
Resolution:
On the keypad of the drive, you will press the dial and go to the following:
Freewheel Stop Always: ConF > FULL > FUn- > Stt > Stt and set to nSt
Run permissive input: ConF > FULL > FUn- > Stt > nSt and assign that to a Logic/Digital Input.
**Keep in mind that Freewheel Stop [nSt] is an active Low input, so if you do not have the wiring in place, the drive will be locked in nSt state. Add a jumper from 24v to DIx/LIx assigned input until you have the actual contact installed.
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.