What would cause the ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot?
Causes for an ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot.
Product Line:
ATV630 with
Environment:
All
Cause:
ATV630 drives firmware is not at 1.5 or greater or you may need to build a project offline and then import the program into Somove.
Resolution:
Checked option 1 and it shows Ethernet IP card. option 2 is no
Drive firmware is Version 1.5IEXX or greater which is good for the Ethernet IP option card.
Next Open up the Somove software:
Checked and we created a project offline adding the Ethernet IP card for option A
Now we copied the program from the drive and now it shows up as Ethernet IP under slot A in the Field bus section under Parameter list.