Why does the S-Flex with bypass not follow deceleration ramp time and freewheel stops instead?

Issue:
Why does an S-Flex with bybass only allow a  freewheel stops instead of rramp?

Product:
SFD212, S-Flex with Bypass

Environment:
All

Cause:
Drive will not follow deceleration time.

Resolution:
SFD212(S-Flex) with bypass will not follow the deceleration time (DEC). This is because when the stop command is given, the drive output contactor (DOC) drops out immediately, causing the run permissive on the R terminal (F112= 1) to drop out and the motor is no longer connected to the VFD. The motor then coasts (freewheel) to a stop.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings