{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Populaire vragen (FAQ's) zoeken
What are the switchgear control failure codes in Easergy T300?
Whenever a command is issued a code appears in the event log for each control operation. These are the following codes and the reasons indicating the status of each control operation.
CODEREASON
0 Command completed successfully
1Local command blocked because switch position is intermediate or unknown
2Local command blocked because switch position is already in correct state
3Local command cancelled by user
4Switch position did not change within configured maximum operation time
5Command blocked by Head Unit interlocks, e.g. motor supply fault or battery low
6Command failed due to timeout waiting for enable from Head Unit
7Local command blocked because disabled by configuration
8Local command blocked because local/remote status is unknown
9Local command blocked because local/remote status is remote
10Local command blocked because automation is ON
11Remote command blocked because automation is ON
12 Sectionalizer command blocked because automation is OFF
13Sectionalizer command blocked because local/remote status is unknown
14Sectionalizer command blocked because local/remote status is remote
15Unexpected command source (firmware error)
16Remote command blocked because requested position is not a valid value
17Command blocked because a command is already in progress for this module
18Command blocked because the power shutdown signal is active
19Command blocked because a command is already in progress for another module
20Command blocked because measured switch position is intermediate or unknown
21Command blocked because measured switch position is same as the requested position
22Command blocked because earth switch position is not closed
23Open command blocked because external input is false
24Open command blocked because external input is true
25Close command blocked because external input is false
26Close command blocked because external input is true
27Commands blocked because module behaviour mode is OFF

Schneider Electric Belgium

bijlage(n)
What are the switchgear control failure codes.pdf [236.22 KB]