How to make the PWD_DIAG and PWD_CMD work upon M580 HSBY swap
Question:
By default, customer found the function blocks PWD_DIAG and PWD_CMD for BMX CPS 4022 were not working properly upon M580 HSBY swap.
How to make the PWD_DIAG and PWD_CMD work upon M580 HSBY swap?

Answer:
It’s the known restriction for M580 HSBY that during a Switchover event, asynchronous communication function blocs which use internal management parameters do not automatically resume operation on the new Primary PLC without special care.

Program your application so that all EFBs instances are not exchanged with Standby PLC. To do this, de-select the Exchange on STBY attribute for the EFB instance

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

  • Selecteer zelf het juiste product

    Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

  • Offerte aanvragen

    Dien uw aanvraag online in en een expert zal contact met u opnemen.

  • Verkooppunten

    Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

  • Help Center

    Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings