What causes an OH Fault on an ATV212 S-Flex?
Getting OH Fault on an ATV212 S-Flex.
Product Line:
Altivar 212 S-Flex enclosed drives
Environment:
All
Cause:
OH fault on the drive display
Resolution:
This is a drive overheating fault.
Causes:
• The ambient temperature is too high.
• An enclosure air vent is blocked.
• A heat source is too close to the drive.
• The drive heatsink temperature sensor is malfunctioning.
Remedies:
• Decrease the ambient temperature by increasing the free space around the drive and removing any heat generating source from the proximity of the drive.
• Check the fan operation
If the cooling vents and fans are not blocked, the fans are running properly, and the ambient temperature is ok, then the drive has an issue and needs repair/replacement.