{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Populaire vragen (FAQ's) zoeken
How can I configure the ATV320 drive for more torque at low speeds?
Issue:
Needs to configure the ATV320 drive for more torque at low speeds.

Product Line:
Altivar 320

Environment:
All

Cause:
Wiring

Resolution:
Go to ConF > FULL > SEt > UFr to increase IR Compensation to 140, set Control Type to Standard.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie