Can the ATV630 and ATV930 Process Drive be used on a Resistance Grounded (IT), Corner Grounded or Ungrounded power System?
Issue:
Can the Process Drive be used on a different types of 3 phase power connectoins?
Product Line:
Process Drive
Environment:
All
Cause:
IT system
Ungrounded system
Corner grounded delta
Resolution:
Yes. With any of these systems the internal EMC Filter must be disconnected according to the instructions in the Installation Manual.
ATV600 Installation manual link: https://www.se.com/ww/en/download/document/EAV64301/
ATV900 Installation manual link: https://www.se.com/ww/en/download/document/NHA80932/
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team. If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)