There is a minimum firmware version for Unity Momentum processors at PV07 or greater.

Issue
Unity Momentum 171CBUx980x processors at a PV07 or greater require a minimum firmware version of 2.0.  PV07 processors cannot be downgraded to firmware versions less than 2.0.

Failure to follow these instructions may result in equipment damage.

It is recommended to upgrade to the latest firmware version.



Product Line
171CBUx980x - Unity Momentum Processors


Resolution
Unity Momentum 171CBUx980x processors at a PV06 or less can be upgraded or downgraded to any version without restriction.

Reference '171CBUx809x_Firmware History_SV2.01.pdf'


Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings