How do I initiate a backup on my LTMCUF keypad

Issue:
Tesys T unit with LTMCUF keypad shows F09 fault code when powered.  Customer is not using the FDR function.

Product line:
Tesys T, LTMR, LTMCUF

Environment:
Tesys T systems equipped with LTMCUF remote keypad.

Cause:
On initial power a backup function must be performed to backup a copy of the program to the LTMCUF keypad.

Resolution:
To initiate a backup function, press and hold the 2 round buttons with green circles around them for 3-4 seconds.  This will initiate a backup function and save a copy of the current program on the Tesys T into the keypad.   After this has completed, cycle power on the LTMR and it should boot without the F09 fault code.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings