M580 ERIO architecture and swap behaviour - ERIO Input management

In an M580 ERIO architecture, let’s consider 3 different use cases for Hot Standby hot swap:

1 - Send swap command via DDT control bit -> swap is OK, inputs are properly managed by default / by design
2 - Power off primary rack -> swap is OK, inputs are properly managed by default / by design
3 - Disconnect/remove both ERIO cables on the Primary CPU
Standby will take over, but Inputs bump to 0 could be visible depending on task duration.
If you are concerned by the 3rd use case, to work around this behavior you need to consider the drop health bit: e.g. RACK1_MOD_COM.DROP_COM_HEALTH

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings