What can cause a Load Slipping (ANF) fault on an ATV340 series drive?

Issue:
ATV340 drive shuts down with ANF Load Slipping Fault.

Product Line:
ATV340 series

Environment:
In applications using an encoder

Cause:
The difference between the output frequency and the speed feedback is not correct.

Resolution:
  • Confirm the drive rating according to the application (motor, load, and so on.)
  • Verify the motor, gain, and stability parameters.
  • Add a braking resistor.
  • Verify the mechanical coupling and wiring of the encoder.

If the torque control function is used and if the encoder is assigned to speed feedback:
  • Set [Load slip detection] Sdd = [No] no.
  • Set both [Positive deadband] dbp and [Negative deadband] dbn to a value less than 10% of the nominal motor frequency.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings