Building Operation Workstation Error window notices:
- A problem has occurred in this application.
More info:
Could not load file or assembly 'SE.Script.Wrapper, Version=1.9.xx...
The system cannot find the file specified.
Cause:
File corrupted or lost
Steps:
1. Check folder : C:\Program Files (x86)\Schneider Electric StruxureWare\Building Operation 1.9\WorkStation\Script...
2. Delete/Rename original corrupted file: SE.Script.Compiler.Wrapper.dll
3. Run WorkStation Installation - Repair current version
4. Start WorkStation
- A problem has occurred in this application.
More info:
Could not load file or assembly 'SE.Script.Wrapper, Version=1.9.xx...
The system cannot find the file specified.
Cause:
File corrupted or lost
Steps:
1. Check folder : C:\Program Files (x86)\Schneider Electric StruxureWare\Building Operation 1.9\WorkStation\Script...
2. Delete/Rename original corrupted file: SE.Script.Compiler.Wrapper.dll
3. Run WorkStation Installation - Repair current version
4. Start WorkStation