Issue
Try to use Management Console's "Deactivate Alarms" feature, as a non-admin user, to deactivate one or more of those active alarms and the following error will appear:
"an unexpected condition was encountered while initializing the AlarmInactivator: Write to Primary data queue failed.."
Product Line
Power Monitoring Expert 9.0
Envorinment
Management Console - "Deactivate Alarm" feature
Cause
PME's MQ setup uses the "Everyone" bucket for permissions and permissions set for the "Everyone" group DO NOT APPLY to domain users by default.
Resolution
Resolution 1:
Run Management Console "As Administrator" (i.e. the right-click menu in Windows).
Resolution 2:
1. Log in as administrator of the server
2. Open the Windows Start menu and search "Computer Management"
3. Open Computer Management then expand Services and Applications > Message Queues
4. Check permissions for all of the private queues by right-clicking on each of them and selecting Properties > Security
- List of private queues to check:
- cloudagent_control
- cloudagent_data
- logsubsystemprimaryrouter_control
- logsubsystemprimaryrouter_data
- logsubsystemsecondaryrouter_control
- logsubsystemsecondaryrouter_data
- Make sure each of the queues listed above have the following permissions:
- "Everyone" group has access to allow:
- Get Properties
- Get Permissions
- Send Message
- "Administrators" group should have full access to the queue
- "ANONYMOUS LOGON" Group should only have access to:
- Send Message
- "Everyone" group has access to allow:
- Get Properties
- Get Permissions
- Send Message
Gepubliceerd voor: Schneider Electric Belgium


Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.