PME9.0 / PME2020 - Measurement Selector in Reports shows blank
When selecting a measurement to run any report, the list remains blank (refreshing it does not solve the issue).
Product Line
Power Monitoring Expert 9.0, Power Monitoring Expert 2020
Environment
Web Application - Reports - Measurement Selector
Cause
A possible cause for this issue is the Web Application Localization being different than the Web Application Language (The are no error messages in the logs for this issue.)
Resolution
- Open Web Applications and navigate to Settings--> Localization.
- Change the language to be something else than it is at the moment (English for instance).
- Save the changes and refresh the browser for it to take effect.
- Switch the language back to the desired one. Save and refresh the browser.