Power Monitoring Expert v8.2/v9.0 /PME2020: CM2000 driver provides incorrect firmware version

Issue
PME 2020 and in previous versions show the firmware version of the CM2000 series meters incorrectly, both in Vista and in the Diagnostics. This intern has an impact on Power Advisor as well.

Environment
Power Monitoring Expert v8.2/v9.0 /PME2020

Cause
Bug with the PME driver.

Resolution

Note: Refer Readme.txt document available with each version to know about the steps to apply the fix.

For more information on
How to determine the firmware version of CM2000 series meters via Front Panel or remotely by software’ refer FAQ - FA211882
What is the minimum firmware requirements for Powerlogic meters in StruxureWare Power Monitoring Expert?’ Refer to FAQ - FA210274

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings