How do contacts 95-96 and 97-98 operate on the LTMR product?

Issue:
Contacts 95-96 and 97-98 do not appear to be operating properly.

Product Line:
Tesys T LTMR motor controllers.

Environment:
All models, All serial numbers.

Cause:
Unexpected operation

Resolution:
Contacts 95-96 are labeled as Normally Closed but are open when de-energized.  Contacts 97-98 are labeled as Normally Open but are closed when de-energized.   When power is applied to the LTMR, the unit will perform a self test which usually completes in 7 to 10 seconds, but may take as much as 30.   After the Power On Self Test has completed, if no faults are found, the relay will be energized internally and contact 97-98 will open, 95-96 will close.   This is normal operation.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings