Product Line
EcoStruxure Panel Servers
Environment
EcoStruxure Power Commission + PAS600L
Issue
PAS600L is blinking orange after the deletion of a connected Modbus device with EcoStruxure Power Commission (EPC).
Cause of Issue
This is a known issue when you delete a Modbus device with EPC.
Resolution
Connect to the Web Pages of the PAS600L and delete the product(s) from the Maintenance -> Devices Communication menu.
Refer to the pictures below.

EcoStruxure Panel Servers
Environment
EcoStruxure Power Commission + PAS600L
Issue
PAS600L is blinking orange after the deletion of a connected Modbus device with EcoStruxure Power Commission (EPC).
Cause of Issue
This is a known issue when you delete a Modbus device with EPC.
Resolution
Connect to the Web Pages of the PAS600L and delete the product(s) from the Maintenance -> Devices Communication menu.
Refer to the pictures below.