Wiring & Programming Status Relays R1 & R2 on the ATV340 Drive
Issue:
How are the relays for ATV340 drive programmed?

Product Line:
Altivar 340

Cause:
Relay programming.

Resolution:
2 relays available R1 and R2.
R1 can be wired as normally-open (R1A and R1C) or normally-closed (R1B and R1C).
R2 is normally-open only.

To program relays:
[Complete settings] -> [Input/Output] -> [Relay] -> [R1 configuration] or [R2 configuration], depending on preference.

See attachment for relay programming, relay delay time, relay active at, holding time, and relay fall back assignments.

Schneider Electric Belgium

bijlage(n)
Relay Configuration ATV340.pdf [655.01 KB]
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

  • Selecteer zelf het juiste product

    Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

  • Offerte aanvragen

    Dien uw aanvraag online in en een expert zal contact met u opnemen.

  • Verkooppunten

    Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

  • Help Center

    Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings