What is the function of PLC input ON/OFF on TeSys Giga contactor ?

Normally the contactor operation is controlled by AC or DC control voltage input to A1-A2terminals. But in advanced version contactor, the contactor can be controlled by additional 24V DC PLC inputs to X1-X2-X3 terminals.

When the PLC switch is ON, the contactor function is controlled by PLC input.
When the PLC switch is OFF, the contactor is controlled by control voltage input to A1-A2.


image.png

The electrical schematic and function description are available on the installation guide DOCA0189EN and here is the link:TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings