Issue
How to run safety task automatically after power cycle in M580 safety CPU ?
Product line Envirovment
Control Expert, Unity Pro, Modicon M580 safety
Environment
Windows 10 64 bits ,Windows Server 2019 64 bits
Resolution
A warm start causes each process task – including the (MAST, FAST, AUX0, AUX1) tasks – to re-enter its operating state as of the time of the power interruption. By contrast, a warm start causes the SAFE task to enter the STOP state, unless Automatic start in RUN is selected.

How to run safety task automatically after power cycle in M580 safety CPU ?
Product line Envirovment
Control Expert, Unity Pro, Modicon M580 safety
Environment
Windows 10 64 bits ,Windows Server 2019 64 bits
Resolution
A warm start causes each process task – including the (MAST, FAST, AUX0, AUX1) tasks – to re-enter its operating state as of the time of the power interruption. By contrast, a warm start causes the SAFE task to enter the STOP state, unless Automatic start in RUN is selected.