Issue:
M171 supported Modbus function codes
Product Line:
M171, EcoStruxure Machine Expert HVAC
Resolution:
Below is the list of supported Modbus function codes of Modicon M171âs Modbus RTU master
- Read Coils â Function 01 (0x01): reads one or more 1-bit read-write objects;
- Read Discrete Inputs â Function 02 (0x02): reads one or more 1-bit read-only objects;
- Read Holding Registers â Function 03 (0x03): reads one or more 16-bit read-write objects;
- Read Input Registers â Function 04 (0x04): reads one or more 16-bit read-only objects;
- Write Single Coil â Function 05 (0x05): writes a single 1-bit read-write object;
- Write Single Register â Function 06 (0x06): writes a single 16-bit read-write object;
- Write Multiple Coils â Function 15 (0x0F): writes one or more 1-bit read-write objects;
- Write Multiple Registers â Function 16 (0x10): writes one or more 16-bit readwrite objects
Gepubliceerd voor:Schneider Electric Belgium