Issue:
REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC.
Product Line:
Vijeo Designer, M340
Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an M340 PLC the double word order must be "Low word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.

Ensure that the Double Word word order is set to "Low word first"

REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC.
Product Line:
Vijeo Designer, M340
Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an M340 PLC the double word order must be "Low word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.
Ensure that the Double Word word order is set to "Low word first"